Draware A/S
Draware A/S er en virksomhed mod kræftAAA Gazelle
RSSNyhedsbreveUdtalelserEventsYouTubeBlogspot
Søg 

3-Phase Power Transducer, Balanced or Unbalanced

3-Phase Power Transducer, Balanced or Unbalanced (ENVIROMUX-PT1M-208-0800, ENVIROMUX-PT3M-208-0800, ENVIROMUX-PT3S-480-0100)
 

Køb nu

3-Phase Power Transducer, Balanced or Unbalanced (ENVIROMUX-PT1M-208-0800, ENVIROMUX-PT3M-208-0800, ENVIROMUX-PT3S-480-0100)
 

Funktioner:

  • Monitors and reports kW real power of any 3 phase circuit, such as the power a building consumes.
  • Split-core design allows installation of CT without disconnecting conductor.
  • Color coded CT and voltage leads.
  • Smart electronics in sensors automatically detect phase reversal.
  • Input primary voltage: 208/240 or 480 VAC RMS
  • Number of phases monitored: one or three
  • Balanced Loads: one CT model (assumes single reading represents all phase currents)
  • Unbalanced Loads: three CT model, one black, red, and yellow.
  • Frequency: 50/60Hz
  • Maximum primary current: Up to 2400 amps continuous per phase
  • Accuracy: +/- 1%
  • Output: 4-20mA
  • Supply power (current loop): 9-30VDC; 30mA max.
  • Requires the ENVIROMUX-S420MA to operate.
  • Caution: sensors tie directly into the line; should be installed by qualified electricians only.
  • Make sure electrical service is disconnected before making any electrical connections.
Overlay